1.Product standard:
The production standard for anti-flaming and fire-resistant cables is GB/T19666-2005,GB/T5023-2008,JB/T8734-2012
2.Main of cables feature
1. Uo/U is 450/750V,300/500,
2. Long-term allowable temperature of the cable:The allowable temperature of 105 Cable should not exceed105ºC;the allowable temperature of other models should not exceed 70ºC.
3. Application:
Applicable to the cables and wires of rated yolatage 450/750V and less than 450/750V AC for power plant,household electrical applance,insurment and telecommunication equipment.
Nominal section(mm2) | Insulation Thickness(mm) | Sheath thickness(mm) | Max.Ave.OD(mm) | Max.D.C.resistance of copper conductor (20ºC) | Min.Insu.resisitance at 70(MΩ.km) | |
Non electroplating | Electroplating | |||||
H05VV-F2*0.75 H05VVH2-F2*0.75 | 0.6 | 0.8 | 7.2 4.5*7.2 | 26 | 26.7 | 0.011 |
H05VV-F2*1.0 H05VVH2-F2*1.0 | 0.6 | 0.8 | 7.5 4.7*7.5 | 19.5 | 20 | 0.010 |
H05VV-F2*1.5 H05VVH2-F2*1.5 | 0.7 | 0.8 | 8.6 5.2*8.6 | 13.3 | 13.7 | 0.010 |
H05VV-F2*2.5 | 0.8 | 1.0 | 10.6 | 7.98 | 8.21 | 0.095 |
H05VV-F2*2.5 | 0.8 | 1.1 | 12.1 | 4.95 | 5.09 | 0.0078 |
H05VV-F 2*4.0 | 0.8 | 0.8 | 7.6 | 26 | 26.7 | 0.011 |
H05VV-F3*1 | 0.6 | 0.8 | 8.0 | 19.5 | 20 | 0.010 |
H05VV-F3*1.5 | 0.6 | 0.9 | 9.4 | 13.3 | 13.7 | 0.010 |
H05VV-F3*2.5 | 0.7 | 1.1 | 11.4 | 7.98 | 8.21 | 0.095 |
H05VV-F3*4.0 | 0.8 | 1.2 | 13.1 | 4.95 | 5.09 | 0.0078 |
H05VV-F4*0.75 | 0.8 | 0.8 | 8.3 | 26 | 26.7 | 0.011 |
H05VV-F4*1 | 0.6 | 0.9 | 9.0 | 19.5 | 20 | 0.010 |
H05VV-F4*1.5 | 0.6 | 1.0 | 10.5 | 13.3 | 13.7 | 0.010 |
H05VV-F4*2.5 | 0.7 | 1.1 | 12.5 | 7.98 | 8.21 | 0.095 |
H05VV-F4*4.0 | 0.8 | 1.2 | 14.3 | 4.95 | 5.09 | 0.0078 |
H05VV-F5*0.75 | 0.8 | 1.4 | 9.3 | 26 | 26.7 | 0.011 |
Laid indoors, and in tunnels, pipelines(include cable duct), and can not bear external mechanical forces.
Technical data:
Rated voltage:450V/750V
Maximum Conductor Temperature:
under normal (70°C), emergency (110°C) or short circuit no more than 5 s (250°C) conditions.
Min. Ambient Temp. 0°C, after installation and only when cable is in a fixed position
Min. Bending Radius: 20 x cable O.D for single-core non-armoured cables
Products Show
Exhibition:
Certificates
Packaging & Shipping
All cable For exporting are well packed and protected by wooden drum or Wood and Steel Drum.
The packing material is depended on the weight and size of cable.
The good information, manufacture information, and the client's information is firmly printed on each size of drum.
After the well packed cable drums sent to Sea Port, they are loaded into 20 FT container or 40 FT container. All cable drum are firmly fixed by safety belt to make sure, no movement during the sea freight.
The size of the container is chosed according to weight of total loaded goods or as per the client's requirement.