600/1000V 4 Core X 300mm2 Cable

1.Stranded Copper Wire
2.Steel Wire Armour or Steel Tape Armour
3.XLPE 11kv Power Cable
4.AC Power Cable
Chat Now

Product Details

1 Product Standard
This product is manufactured according to GB/T12706.1, equivalent to IEC60502.1. Or BS, DIN, ICEA standard as customer request.  
 
2 Application
The product is suitable for power transmission and distribution lines with rated power frequency voltage up to and including 0.6/1KV.
Operating Performance
1). Rated power frequency voltage Uo/U: 0.6/1KV.
2). Max. Permissible continuous operating temperature of conductor: 90ºC
3). Max. Short-circuit temperature of the conductor shall not exceed: (5S maximum duration) 250ºC
4). The ambient temperature under installation should not below 0ºC
5). The bending radius of a cable should not be less than 15 times of the cable diameter.
6). The test voltage (A.C.): 3.5kV/5min.
7). The flame-retardant properties of cable comply with grade A, B, C of GB/T19666-2005 or IEC60332.
 

Electric cable (517)3 Construction:
 

Standard: BS6622, BS EN/IEC 60228,IEC60502.2
Conductor: Class 2 stranded plain copper conductor to BS EN 60228:2005 (previously BS6360)
Conductor screen: Semi-conducting material
Insulation: XLPE (Cross-Linked Polyethylene) Type GP8 to BS7655
Insulation Screen: Semi-conducting material
Metallic Screen: Individual and overall copper tape screen to BS6622
Filler: PET (Polyethylene Terephthalate) fibres
Separator: Binding tape
Bedding: PVC (Polyvinyl Chloride) Type TM1 to BS7655
Armouring:

Single Core: Aluminium Wire Armoured (AWA)
MultiCore: Steel Wire Armoured (SWA)
Sheath: PVC (Polyvinyl Chloride) Type TM1 to BS7655
Colour: Red or Black

Electric cable (595)
4 Type and Name:

TypeDesignationApplications
YJVCopper conductor,XLPE insulated,PVC sheathed power cableFor laying indoors,in tunnel or cable trench,unable to bear external mechanical forces.
Single core cable is not allowed to laid in magnetic duct.
YJLVAluminum conductor,XLPE insulated,PVC sheathed power cable
YJYCopper conductor, XLPE insulated,PE sheathed power cable
YJLYAluminum conductor, XLPE insulated,PE sheathed power cable
YJV22Copper conductor,XLPE insulated,steel tape armoured,PVC sheathed power cableFor laying indoors,in tunnel in cable trench,or direct in ground,
able to bear external mechanical forces.Single core cable is not allowed to laid in magnetic duct.
YJLV22Aluminum conductor,XLPE insulated,steel tape armoured,PVC sheathed power cable
YJV23Copper conductor,XLPE insulated,steel tape armoured,PE sheathed power cable
YJLV23Aluminum conductor,XLPE insulated,steel tape armoured,PE sheathed power cable
YJV32Copper conductor,XLPE insulated,steel wire armoured,PVC sheathed power cableFor laying indoors,in tunnel cable trench,well or direct in ground,
able to bear external mechanical forces and certain pulling force.
YJLV32Aluminum conductor,XLPE insulated,steel wire armoured,PVC sheathed power cable
YJV33Copper conductor,XLPE insulated,steel wire armoured,PE sheathed power cable
YJLV33Aluminum conductor,XLPE insulated,steel wire armoured,PE sheathed power cable

 
 5 Specification:

TypeNo. of coresNom. Cross-section of conductor
(mm2)
Copper conductorAluminum conductor
YJV  YJY-11.5-800
-YJLV  YJLY2.5-800
YJV22  YJV23YJLV22  YJLY2310-800
YJV  YJY-21.5-300
-YJLV  YJLY2.5-300
YJV22  YJV23YJLV22  YJLY234.0-300
YJV32  YJV33YJLV32  YJLY3310-300
YJV  YJY-31.5-400
-YJLV  YJLY2.5-400
YJV22  YJV23YJLV22  YJLY234.0-400
YJV32  YJV33YJLV32  YJLY3310-400
YJV  YJY-41.5-400
-YJLV YJLY2.5-400
YJV22  YJV23YJLV22  YJLY234.0-400
YJV32  YJV33YJLV32  YJLY3310-400
YJV  YJY-3+11.5-400
-YJLV  YJLY4.0-400
YJV22  YJV23YJLV22  YJLY234. 0-400
YJV32  YJV33YJLV32  YJLY3310-400
YJV  YJY-51.5-400
-YJLV  YJLY2.5-400
YJV22  YJV23YJLV22  YJLY234.0-400
YJV32  YJV33YJLV32  YJLY3310-400
YJV  YJY-4+11.5-400
-YJLV  YJLY4.0-400
YJV22  YJV23YJLV22  YJLY234. 0-400
YJV32  YJV33YJLV32  YJLY3310-400
YJV  YJY-3+21.5-400
-YJLV  YJLY4.0-400
YJV22  YJV23YJLV22  YJLY234. 0-400
YJV32  YJV33YJLV32  YJLY3310-400
The armoured single core cables are used for D.C. system only. As for A.C. system,non-magnetic armour material should be used, or a magnetic isolation should be applied.

Electric cable (22)

Hot Tags: 600/1000v 4 core x 300mm2 cable, China, manufacturers, suppliers, factory