Medium Voltage Power Cable Underground 11kv 15kv 33kv XLPE Power Cable

Conductor: Circular stranded copper conductor, conforms to IEC 60228 class 2
Insulation: XLPE/A
Inner Covering: PVC
Armour: Galvanized Steel Wire or tape
Sheath: PVC type ST2 to IEC 60502, black
Note: Insulation color as per standards or customer requirement
Chat Now

Product Details

Medium Voltage Power Cable Underground 11kv 15kv 33kv XLPE Power Cable

Product Description

Applications

These cables are used for electricity supply in low voltage installation system, They are suitable for installation in indoors and outdoors, in cable ducts, under ground, in power and switching stations, local energy distributions, industrial plants, where there is no risk of mechanical damage.

Construction

Conductors

The conductors shall be either of Class 1 or Class 2 of plain or metal-coated annealed copper or of plain aluminium or aluminium alloy, or of Class 5 of plain or metal-coated copper in accordance with IEC 60228.

Insulation

XLPE material and thickness shall be as per IEC 60502 or BS 5467 rated for 90C continuous operation.

Colour Code

Colour Code (1)

1 CoreRed or Black
2 CoresRed, Black
3 CoresRed, Yellow, Blue
4 CoresRed, Yellow, Blue, Black
5 CoresRed, Yellow, Blue, Black, Green
Above 5 CoresBlack Cores with White numerals

Colour Code (2)

1 CoreBrown or Blue
2 CoresBrown, Blue
3 CoresBrown, Black, Grey
4 CoresBlue, Brown, Black, Grey
5 CoresGreen/Yellow, Blue, Brown, Black, Grey
Above 5 CoresBlack Cores with White numerals

Other colours can be manufactured upon request.

 
Assembly / Inner Covering

The inner coverings may be extruded or lapped. For cables with circular cores, except cables with more than five cores, a lapped inner covering shall be permitted only if the interstices between the cores are substantially filled. A suitable binder is permitted before application of an extruded inner covering. The material is compatible with the insulating material,The materials used for inner coverings and fillers shall be suitable for the operating temperature of the cable and compatible with the insulating material.For halogen free cables, the inner covering and fillers shall also be halogen free compound.

 
Armour

Aluminum/galvanized steel/steel wires applied helically over the Inner Covering as per IEC 60502-1, or double aluminum/steel tapes and copper/tinned copper wire can also be manufactured upon request.
 

Outer Sheath

Outer sheath shall be of extruded PVC Type ST1/ST2 as per IEC 60502-1, Polyethylene type ST3/ST7, Halogen free compound ST8, Polychloroprene, chlorosulfonated polyethylene or similar polymers, type SE1 are also available on request.

Fire Performance of Cable Sheaths

Cables can be supplied with special flame retardant PVC outer sheath to comply with the flame test requirements of IEC 60332-3-22, IEC 60332-3-23 and IEC 60332-3-24, Halogen Free material comply to IEC60754-1/2 and IEC 60684-2.

 

Core Identification:

1 Core: Brown 

2 Cores: Brown, Blue 

3 Cores: Brown, Black, Grey 

4 Cores: Blue, Brown, Black, Grey; 

5 Cores: Green/Yellow, Blue, Brown, Black, Grey 

Alternative core identification: White Cores with Black numbers


, Model, Name & Application:

ModelNameApplication
YJV,
Copper conductor,XLPE insulated,PVC sheathed electric cable
,.
For laying indoors,in tunnels,cable trench,etc,unable to bear external mechanical forces.
.
Single core cable in magnetic duct is not permissible.
YJLV,
Aluminium conductor,XLPE insulated,PVC sheathed electric cable
YJY,
Copper conductor,XLPE insulated,PE sheathed electric cable
YJLY,
Aluminium conductor,XLPE insulated,PE sheathed electric cable
YJV22,
Copper conductor,XLPE insulated,Steel tape armoured,PVC sheathed electric cable
,,.
For laying indoors,in tunnels,cable trench,or direct in ground.
.
Able to bear external mechanical forces,but unable to bear large pulling forces.
YJLV22,
Aluminium conductor,XLPE insulated,Steel tape armoured,PVC sheathed electric cable
YJV23,
Copper conductor,XLPE insulated,Steel tape armoured,PE sheathed electric cable
YJLV23,
Aluminium conductor,XLPE insulated,Steel tape armoured,PE sheathed electric cable
YJV32,
Copper conductor,XLPE insulated,Steel wire armoured,PVC sheathed electric cable
,,,.
For laying indoors,in tunnels,cable trench,vertical shaft or direct in ground.
.
Able to bear external mechanical forces and some pulling forces.
YJLV32,
Aluminium conductor,XLPE insulated,Steel wire armoured,PVC sheathed electric cable
YJV33,
Copper conductor,XLPE insulated,Steel wire armoured,PE sheathed electric cable
YJLV33,
Aluminium conductor,XLPE insulated,Steel wire armoured,PE sheathed electric cable


Product data:
3.6/6KV, , /
3.6/6KV, 1-Core XLPE Insulated, PVC/PE Sheathed Power Cable


Nominal cross-sectional area  of conductor (mm2)

Insulation thickness (mm)
YJV, YJLV, YJY, YJLYYJV22, YJLV22, YJV23, YJLV23YJV32,YJLV32,YJV33,YJLV33

Approx. overall diameter of cable (mm)

Approx. weight of cable (kg/km)

Approx. overall diameter of cable (mm)

Approx. weight of cable (kg/km)

Approx. overall diameter of cable (mm)

Approx. weight of cable (kg/km)
YJV, YJYYJLV, YJLYYJV22, YJV23YJLV22, YJLV23YJV32, YJV33YJLV32, YJLV33
1×252.517.956039021.770055024.713401190
1×352.518.968048022.682061025.814901290
1×502.520.386055024.099069027.217201420
1×702.521.9108065025.4122079028.820101590
1×952.523.7135076027.2149092030.623501770
1×1202.525.2161087028.71770104032.126801950
1×1502.527.0192099031.72240133034.930702160
1×1852.528.62290114033.32600148036.534802360
1×2402.631.22860137035.93180173039.141402680
1×3002.834.03500164038.73810199041.948403020
1×4003.037.64610214042.54840242045.663203890
1×5003.241.35700261046.35860283049.374704440
1×6303.244.96990309050.07200338053.189405120

3.6/6KV, , /
3.6/6KV, 3-Core XLPE Insulated, PVC/PE Sheathed Power Cable


Nominal cross-sectional area  of conductor (mm2)

Insulation thickness (mm)
YJV, YJLV, YJY, YJLYYJV22, YJLV22, YJV23, YJLV23YJV32,YJLV32,YJV33,YJLV33

Approx. overall diameter of cable (mm)

Approx. weight of cable (kg/km)

Approx. overall diameter of cable (mm)

Approx. weight of cable (kg/km)

Approx. overall diameter of cable (mm)

Approx. weight of cable (kg/km)
YJV, YJYYJLV, YJLYYJV22, YJV23YJLV22, YJLV23YJV32, YJV33YJLV32, YJLV33
3×252.535.81750128040.52760230042.736203160
3×352.538.12130147043.03210255046.241403490
3×502.541.12670174046.13830289049.348603940
3×702.544.53390209049.74650334052.957704480
3×952.548.54250247053.85630385057.068705120
3×1202.551.75090285057.26550431060.478705650
3×1502.555.46120331060.97650484064.290906320
3×1852.558.87270380064.58890543067.8104607050
3×2402.664.69090460070.510860637075.1133808940
3×3002.870.611120551076.713230761081.31568010130
3×4003.078.415190775086.2178301044089.51932011930
3×5003.286.217131804594.3200871125697.62306013820
3×6303.294.0210379749102.42395213166105.72769016050

6/6  6/10KV, , /
6/6  6/10KV, 1-Core XLPE Insulated, PVC/PE Sheathed Power Cable


Nominal cross-sectional area  of conductor (mm2)

Insulation thickness (mm)
YJV, YJLV, YJY, YJLYYJV22, YJLV22, YJV23, YJLV23YJV32,YJLV32,YJV33,YJLV33

Approx. overall diameter of cable (mm)

Approx. weight of cable (kg/km)

Approx. overall diameter of cable (mm)

Approx. weight of cable (kg/km)

Approx. overall diameter of cable (mm)

Approx. weight of cable (kg/km)
YJV, YJYYJLV, YJLYYJV22, YJV23YJLV22, YJLV23YJV32, YJV33YJLV32, YJLV33
1×253.419.860945823.491976726.616431384
1×353.420.872951424.4105584027.618211499
1×503.422.387658525.7121992929.120271628
1×703.423.8109268127.21458104730.623291810
1×953.425.7138880529.11780119732.526891999
1×1203.427.1165191331.92312157533.930372192
1×1503.428.71970104333.52670174335.734192384
1×1853.430.42271116535.23007190138.441472869
1×2403.432.92830138237.736212173<span style="box-sizing: border-box; font-family: Arial, Helvetica%                                    